Products

DAM-3019DA
AC Input |
|
Input Channel |
8-way AC mains switch input detection |
Signal Type |
0V~250VAC |
Logic Level |
Logic 0: 0~25VAC Logic 1: 80V~250VAC |
Isolation Method |
Optical isolation |
Digital Input |
|
Input Channel |
6 digital inputs |
Input Type |
Dry/Wet Contact |
Wiring |
common cathode |
Logic Level |
Dry contact: Logic 0: short to DGND Logic 1: open circuit Wet Contacts: Logic 0: 0~3VDC Logic 1: 5V~30VDC |
Operating Mode |
DI input |
Isolation Voltage |
1500Vrms |
Others |
|
Communication Interface |
RS485 |
RS485 Transfer Rate Note 1 |
Maximum 180 times/second (total channel of single module, under 115200bps) Maximum 24 times/second (total channel of single module, under 9600bps) Maximum 3 times/second (total channel of single module, under 1200bps) |
Baud Rate |
1200~115200bps |
Watchdog |
internal gate dog |
Supply Voltage |
DC 10V~30V |
Power Protection |
Power reverse protection |
Power Consumption |
0.5W/24VDC |
Operating Temperature |
-10℃~+70℃ |
Storage Temperature |
-20℃~+85℃ |
Note:
RS485 Transfer Rate: This parameter refers to the communication speed between the MCU controller and the host computer.
©2019 Beijing Art Technology Development Co., Ltd., All rights reserved 京ICP备09023590号 Powered by www.300.cn