Products

DAM-3535N
Analog Input |
|
Input Channel |
3 current channels, 3 voltage channels |
Input Type |
voltage input, current input |
Voltage Range (RMS) |
Default 400V (customizable, maximum 450V) |
Current Range (RMS) |
Default 100A (customizable 5A、10A、20A、80A、100A、150A、200A) |
DS18B20 temperature measurement |
1 channel DS18B20 temperature acquisition, can connect 4 sensors |
Output Parameters |
Phase voltage, phase current, line voltage, active power, reactive power, apparent power, power factor, total energy, forward active energy, forward reactive energy, input frequency, three-phase total active power, three-phase total reactive power, three-phase total apparent power, three-phase total power factor, three-phase total positive-phase active energy, three-phase total positive-phase reactive energy, three-phase total power factor, 4-way temperature value |
Acquired Signal |
The collected signal is the grid standard AC signal, and the frequency does not exceed 65Hz |
Sample Rate |
Voltage and current are collected every 400ms, and power and electricity are collected every 300ms |
Resolution |
16 bit |
Acquisition Accuracy |
2‰ |
Current Transformer |
External current transformer, see 1.6 External transformer description |
Energy |
With energy storage |
Secondary Mutual Inductance |
With secondary mutual inductance function |
Isolation Voltage |
3000V |
Other |
|
Communication Interface |
RS485 |
Baud Rate |
1200~115200bps |
Data Transfer Rate |
It is determined by the baud rate and the number of data to be read. If all data is read at one time, it is recommended to read once every second at a baud rate of 9600. |
Watchdog |
Built-in watchdog |
Supply Voltage |
+10V~30VDC |
Power Protection |
Power reverse protection |
Power Consumption |
Rated 0.75W @ 24VDC |
Operating Temperature |
-10℃~+70℃ |
Storage Temperature |
-20℃~+85℃ |
©2019 Beijing Art Technology Development Co., Ltd., All rights reserved 京ICP备09023590号 Powered by www.300.cn